Section 4. BASIC HARD-WIRED ZONES 18
This section provides general information for the hard-wired zones in the system, plus
specific instructions for installing 2-wire smoke detectors, 4-wire smoke/combustion
detectors, and 2-wire latching type glass break detectors.
Installing the Hard-Wired Zones
Common Characteristics for Zones 1–8
EOLR supervised zones supporting both open circuit and closed circuit
devices
As many 4-wire smoke detectors as can be powered from Aux Power on the
control (zones 2–7)
Programmable for 10, 350, or 700 msec response
350 msec (default) should be used for most standard contacts. For
vibration type contacts, 10 msec is more suitable
Wiring Burglary and Panic Devices To Zones 1–8
1. Connect sensors/contacts to the hard-wired zone terminals (8 through 20).
See the Summary of Connections diagram .
2. Connect closed circuit devices in series in the high (+) side of the loop. The
EOL resistor must be connected in series with the devices, following the
last device. See the Summary of Connections diagram.
3. Connect open circuit devices in parallel across the loop. The 2,000 ohm
EOLR must be connected across the loop wires at the last device.
If the EOLR is not at the end of the loop, the zone will not be properly
supervised, and the system may not respond to an open circuit on the zone.
High Resistance Supervision on Hard-Wired Zones 2–8
Special supervision in the control senses high resistance on hard-wired
zone loops 2–8, causing a warning “CHECK” display with the affected zone
number to occur when the system is in the disarmed state. The system
cannot be armed when this display is present. If the system is in the
armed state when the high resistance condition occurs, no display will
take place until the system is disarmed.
Wiring 2-Wire Smoke Detectors To Zone 1
1. Connect 2-wire smoke detectors across zone 1 terminals 8 (+) and 9 (–).
Observe proper polarity when connecting the detectors.
2. If an EOL resistor is presently connected across zone 1 terminals, remove
it. The EOL resistor must be connected across the loop wires at
the last detector.
U
L
In UL installations, only zone 1 may be used as a Fire zone. In addition, an
Ademco Model 610–7 must be used as an End-of-Line resistor at the last
detector.
The alarm current provided by zone 1 will support only one smoke detector in
the alarmed state.
“Verify” Operation of
2-Wire Smoke Detectors
in Zone 1
The control panel will “verify” any alarm by resetting the smoke detectors
after the first alarm trigger, and then waiting 90 seconds for a second alarm
trigger. If the smoke detector or thermostat does not trigger again, the
control will disregard the first trigger, and no alarm signal will occur. This
feature eliminates false alarms due to electrical or physical transients.
This feature is available only on units that report to the downloader as Rev
4 or higher.